Kraus & Naimer CA10B A230 3-Step Cam Switch without OFF, 1-Pole, 20 A, 64 x 64 mm Front Plate

Kraus & Naimer CA10B A230 3-Step Cam Switch without OFF, 1-Pole, 20 A, 64 x 64 mm Front Plate

Kraus & Naimer CA10B A230 is a 1-pole, 20 A step cam switch with 3 steps (1-3) and no OFF position. Technical values: CA10B type, size class S1, 64 x 64 mm front plate; thermal current Ith 20 A (55 °C), enclosed thermal current Ithe 20 A; rated insulation voltage Ui 690 V, rated impulse withstand voltage Uimp 6 kV (switch), 4 kV (switch disconnector); AC-21A 20 A, AC-22A 20 A, AC-15 380–440 V 4 A; maximum gG 25 A fuse, Icw 140 A (1 s); conductor cross-section: solid 0.5–2.5 mm², flexible 0.75–2.5 mm²; tightening torque 0.6 Nm; 1 pole, 2 levels, 3 steps, positions 1-2-3, switching angle 60°. Values are given in accordance with IEC 60947-3 and EN 60947-3. It is used in control and adjustment circuits that need selection between several circuits or steps; none of the 3 positions is an OFF position.

Size TypeS1
Number of Poles1P
Cam Switch Position Count3 Positions
SeriesCA10B
Function CodeA230
Switch FunctionStepped Without Off (1-2-3)
Switch Positions1-2-3
Number of Positions3
Switching Angle60° °
Number of Levels2
Front Plate CodeF076
Front Plate Size (A x B)64 x 64 mm
Rated Current20 A
Conventional Free Air Thermal Current (Ith)20 A
Ambient temperature for rated current55 °C (24 hours, tepe 60 °C)
Conventional Enclosed Thermal Current (Ithe)20 A
Rated Insulation Voltage (Ui)690 V (AC 50/60 Hz)
Rated Impulse Withstand Voltage (Uimp)6 kV (circuit breaker); 4 kV (switch-disconnector)
Overvoltage categoryIII
Pollution Degree3
Rated Operational Current AC-15 (Ie)220–240 V: 6 A; 380–440 V: 4 A
Rated Operational Current AC-20A (Ie)690 V: 20 A
Rated Operational Current AC-21A (Ie)20–690 V: 20 A
Rated Operational Current AC-22A (Ie)220–500 V: 20 A; 660–690 V: 20 A
Rated Operational Power AC-2 (Pe)3-phase: 220–240 V 4 kW; 380–440 V 7.5 kW; 500 V 10 kW; 660–690 V 10 kW
Rated Operational Power AC-3 (Pe)3-phase: 220–240 V 3 kW; 380–440 V 5.5 kW; 500 V 5.5 kW; 660–690 V 5.5 kW. 1-phase: 110–120 V 0.6 kW; 220–240 V 2.2 kW; 380–440 V 3 kW
Rated Operational Power AC-4 (Pe)3-phase: 220–240 V 0.55 kW; 380–440 V 1.5 kW; 500 V 1.5 kW; 660–690 V 1.5 kW. 1-phase: 110–120 V 0.3 kW; 220–240 V 0.75 kW; 380–440 V 1.5 kW
Rated Operational Power AC-23A (Pe)3-phase: 220–240 V 3.7 kW; 380–440 V 7.5 kW; 500 V 7.5 kW; 660–690 V 7.5 kW. 1-phase: 110–120 V 0.75 kW; 220–240 V 2.5 kW; 380–440 V 3.7 kW
Maximum Fuse CurrentgG 25 A
Rated Short-Time Withstand Current (Icw)140 A (1 s)
Breaking Capacity220–240 V: 150 A; 380–440 V: 150 A; 660–690 V: 80 A
Power Loss per Pole0.9 W
Solid Conductor Cable Cross-Section0.5–2.5 mm2
Stranded Conductor Cable Cross-Section2x2.5 mm2
Flexible Conductor Cross-Section0.75–2.5 mm2
Conductor Cross-Section with Ferrule0.5–2.5 mm2
Cable section (AWG/MCM)AWG 14 (flexible); AWG 12 (solid or stranded)
Conductor MaterialCopper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered)
Tightening Torque0.6 Nm (5 lb-in)
Recommended Screw DriverPozidriv/Phillips PH1; slotted 0.8 x 4 mm (DIN 5264)

Shipping & assurance

For made-to-order products, the procurement and carrier hand-over time is shared with the quotation.

In rare cases, all or part of an order may be unavailable due to stock or procurement updates. In this case, the customer is informed and the relevant product is cancelled and refunded. A product being open for sale does not guarantee that it is in physical store stock.