Kraus & Naimer CA10B A253 6-Step Cam Switch without OFF, 2-Pole, 20 A, 64 x 64 mm Front Plate

Kraus & Naimer CA10B A253 6-Step Cam Switch without OFF, 2-Pole, 20 A, 64 x 64 mm Front Plate

Kraus & Naimer CA10B A253 is a 2-pole step cam switch with 6 steps and no OFF position; thermal current 20 A, front plate size 64 x 64 mm. The handle of the CA10B A253 turns in 60° steps through the positions 1-2-3-4-5-6, and each position engages a different contact arrangement; number of levels 6, front plate code F079. It is used in multi-position selection and control circuits. For CA10B A253, rated insulation voltage Ui is 690 V, AC-21A rated current is 20 A, maximum fuse rating is gG 25 A and rated short-time withstand current Icw is 140 A (1 s). Single-phase AC-3 motor rating is 2.2 kW at 220–240 V and 3 kW at 380–440 V. CA10B A253 is connected by screw terminals: flexible conductors of 0.75–2.5 mm², conductors with ferrule of 0.5–2.5 mm² and stranded conductors of 2 x 2.5 mm² can be connected; tightening torque is 0.6 Nm.

Size TypeS1
Number of Poles2P
Cam Switch Position Count6 Positions
SeriesCA10B
Function CodeA253
Switch FunctionStepped Without Off (1-2-3-4-5-6)
Switch Positions1-2-3-4-5-6
Number of Positions6
Switching Angle60° °
Number of Levels6
Front Plate CodeF079
Front Plate Size (A x B)64 x 64 mm
Rated Current20 A
Conventional Free Air Thermal Current (Ith)20 A
Ambient temperature for rated current55 °C (24 hours, tepe 60 °C)
Conventional Enclosed Thermal Current (Ithe)20 A
Rated Insulation Voltage (Ui)690 V (AC 50/60 Hz)
Rated Impulse Withstand Voltage (Uimp)6 kV (circuit breaker); 4 kV (switch-disconnector)
Overvoltage categoryIII
Pollution Degree3
Rated Operational Current AC-15 (Ie)220–240 V: 6 A; 380–440 V: 4 A
Rated Operational Current AC-20A (Ie)690 V: 20 A
Rated Operational Current AC-21A (Ie)20–690 V: 20 A
Rated Operational Current AC-22A (Ie)220–500 V: 20 A; 660–690 V: 20 A
Rated Operational Power AC-2 (Pe)3-phase: 220–240 V 4 kW; 380–440 V 7.5 kW; 500 V 10 kW; 660–690 V 10 kW
Rated Operational Power AC-3 (Pe)3-phase: 220–240 V 3 kW; 380–440 V 5.5 kW; 500 V 5.5 kW; 660–690 V 5.5 kW. 1-phase: 110–120 V 0.6 kW; 220–240 V 2.2 kW; 380–440 V 3 kW
Rated Operational Power AC-4 (Pe)3-phase: 220–240 V 0.55 kW; 380–440 V 1.5 kW; 500 V 1.5 kW; 660–690 V 1.5 kW. 1-phase: 110–120 V 0.3 kW; 220–240 V 0.75 kW; 380–440 V 1.5 kW
Rated Operational Power AC-23A (Pe)3-phase: 220–240 V 3.7 kW; 380–440 V 7.5 kW; 500 V 7.5 kW; 660–690 V 7.5 kW. 1-phase: 110–120 V 0.75 kW; 220–240 V 2.5 kW; 380–440 V 3.7 kW
Maximum Fuse CurrentgG 25 A
Rated Short-Time Withstand Current (Icw)140 A (1 s)
Breaking Capacity220–240 V: 150 A; 380–440 V: 150 A; 660–690 V: 80 A
Power Loss per Pole0.9 W
Solid Conductor Cable Cross-Section0.5–2.5 mm2
Stranded Conductor Cable Cross-Section2x2.5 mm2
Flexible Conductor Cross-Section0.75–2.5 mm2
Conductor Cross-Section with Ferrule0.5–2.5 mm2
Cable section (AWG/MCM)AWG 14 (flexible); AWG 12 (solid or stranded)
Conductor MaterialCopper only (individual strands may be tinned or silver-plated; conductor ends must not be soldered)
Tightening Torque0.6 Nm (5 lb-in)
Recommended Screw DriverPozidriv/Phillips PH1; slotted 0.8 x 4 mm (DIN 5264)