Electrical Engineering Calculators

Calculate cable ampacity (IEC 60364-5-52), voltage drop, busbar capacity (DIN 43671), power factor correction (kVAr), star-delta motor current, transformer short-circuit current and IP/IK protection ratings.

Calculators and reference formulas

CalculatorFormula / StandardScopeRelated product categories
Current and Breaker Size Calculator from Active PowerThree-phase: I = P / (√3 × U × cos φ × η)Calculate the approximate line current of motors, heaters and other electrical loads from their active power.Miniature Circuit Breakers, Molded Case Circuit Breakers (MCCB), Low-Voltage Cables
Cable Current-Carrying Capacity CalculatorCorrected capacity: Iz = Iz₀ × k₁ × k₂Cross-section alone is not enough. The same cross-section carries a different current depending on insulation, installation method, ambient temperature and the number of circuits running side by side.Low-Voltage Cables, N2XH Halogen-Free Cables, NA2XH Aluminum Cables
Busbar Current-Carrying Capacity CalculatorContinuous current: I = I₀ × (Δθ / 30)^0.61 × √(R₆₅ / R)For busbar selection in panels and distribution systems, correct the DIN 43671 (copper) and DIN 43670 (aluminum) continuous current values for ambient and busbar temperature.Busbars and Distribution Blocks, Panels and Equipment
Voltage Drop CalculatorThree-phase: ΔU = √3 × I × L × (R cos φ + X sin φ)Find the voltage at the end of the line and the percentage voltage loss, taking into account how conductor resistance changes with temperature and the reactance of AC lines.Low-Voltage Cables, NYY Underground Cables
AWG to mm² ConverterAWG: d = 0.127 × 92^((36 − AWG) / 39) · kcmil: A = MCM × 0.5067Convert American Wire Gauge and kcmil/MCM sizes to conductor diameter and actual geometric cross-section. For metric cable orders, compare the IEC nominal size that does not drop to a smaller cross-section.Low-Voltage Cables, Signal and Control Cables
Power Factor Correction (kVAr) CalculatorQc = P × (tan φ₁ − tan φ₂) · Three-phase current: Ic = Qc / (√3 × U)Calculate the total capacitor bank power (kVAr), the kVAr/kW factor and the reduction in line current needed to raise the existing power factor to the target cos φ.Power Capacitors, PFC Contactors, Reactive Power Control Relays
Star-Delta and DOL Motor Current CalculatorIn = P / (√3 × U × cos φ × η) · IΔ = In / √3 · IY = In / 3Compare line current, winding branch current (IΔ = In / √3) and star contactor current (IY = In / 3) for direct-on-line (DOL) and star-delta motor starters.Power Contactors, Thermal Overload Relays, Motor Protection Circuit Breakers
Transformer Short-Circuit Current CalculatorIn = S / (√3 × U) · Ik = In / (uk / 100)Find the nominal secondary current at a distribution transformer's terminals and the prospective three-phase short-circuit current (kA) assuming an infinite upstream busbar.Molded Case Circuit Breakers (MCCB), Air Circuit Breakers (ACB), Miniature Circuit Breakers
IP and IK Protection Rating CalculatorIEC 60529: IP [Solid: 0–6][Water: 0–9] · IEC 62262: IK00–IK10 (Joules)Check the meaning of the first and second IP numerals and the corresponding IK impact energy (joules) from the standard tables for panels, boxes and luminaires.Panels and Equipment, Junction Box Enclosures
Cable Type Code and Letter Symbols DecoderVDE: [N/NA][Y/2X][C][Y/H] [-J/-O] · HD 361: [H05/H07][V/R/N]-[U/R/K/F]Look up the conductor, core insulation, screen, outer sheath and rated voltage meaning of VDE and harmonized HD 361 cable type designations.Low-Voltage Cables, Signal and Control Cables, Fire-Resistant Cables
Cable Copper and Aluminum Weight Calculatorm = n × S × ρ · Copper: ρ = 8.89 kg/(km·mm²) · Aluminum: ρ = 2.70 kg/(km·mm²)Calculate the theoretical bare copper or aluminum conductor weight (kg and kg/km) of a cable from core count, nominal cross-section and length.Low-Voltage Cables, Sheet Metal Cable Trunking
Cable Trunking and Conduit Fill CalculatorA₁ = π × d² / 4 · A_total = N × A₁ · A_pathway = A_total / k_fillFind the total external cross-sectional area of your cables from outer diameter and count, and see the required internal area and standard trunking size.Cable Trunking, Panel Wiring Ducts
Current Transformer Ratio and VA Burden CalculatorR_loop = 2 × L × 0.0175 / S · P_wire = I_sn² × R_loop · S_total = S_meter + P_wireSelect the next standard current transformer ratio from line current and calculate total secondary VA burden including copper lead losses.Current Transformers, Power Network Analyzers
Motor Energy Consumption and Efficiency CalculatorP_in = (P_shaft × k_load) / η · ΔE = (P_in1 − P_in2) × t (kWh/yr)Calculate annual electric motor energy consumption (kWh/year) and the kWh savings achieved by upgrading from IE2 to IE3 or IE4 efficiency classes.Motor Protection Circuit Breakers, Motor Starters